Step 6 Install the air filter fasteners.
Step 7 Power on the unit, choose Maint > Performance Maint on the home screen of
the display module, and clear the total runtime of the air filter.
Step 8 Tap Start on the home screen. Ensure that the unit is running normally without
any alarms.
----End
12.4 Replacing an Air Filter (FDC Scenario)
Prerequisites
●
●
●
Procedure
Step 1 On the home screen of the display module, tap Shutdown and turn off the unit
switch in the PDF.
Exercise caution because the unit is still energized after it is shut down on the
home screen of the display module.
Step 2 Replace the outdoor intake air filter. Remove the air filter fasteners and take out
the air filter from the end.
Figure 12-6 Replacing an air filter
Issue 03 (2021-04-20)
An air filter needs to be replaced.
A spare air filter of the same model is available and functional.
When replacing an air filter, you need to use a maintenance platform. For
details how to prepare the platform, see
NO TICE
Copyright © Huawei Digital Power Technologies Co., Ltd.
12 Component Replacement
E Air filter Maintenance
Platform.
156