Huawei FusionCol8000-E24 User Manual page 209

Modular indirect evaporative cooling system
Table of Contents

Advertisement

FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Prerequisites
Procedure
Step 1 On the home screen of the display module, tap Shutdown and turn off the unit
switch in the PDF.
Exercise caution because the unit is still energized after it is shut down on the
home screen of the display module.
Step 2 Open the door of the electric control box.
Step 3 Remove the cables from the faulty relay.
Step 4 Remove the coil. Break the metal plate on the coil and pull out the coil.
Step 5 Remove the base. Remove the coil, press the clip on the faulty base using a flat-
head screwdriver, and pull the base outwards to remove it.
Figure 12-49 Replacing a relay
(1) Base
(4) Metal plate
Step 6 Install a new coil or base.
Step 7 Close the door of the electric control box.
Issue 03 (2021-04-20)
A relay needs to be replaced.
A spare relay of the same model is available and functional.
Tools: Phillips screwdriver, flat-head screwdriver
NO TICE
Copyright © Huawei Digital Power Technologies Co., Ltd.
(2) Coil
12 Component Replacement
(3) Clip ring
200