Huawei FusionCol8000-E24 User Manual page 113

Modular indirect evaporative cooling system
Table of Contents

Advertisement

FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Tab
System
Optional
Parts
Issue 03 (2021-04-20)
Parameter
Return air sensor
Supply air sensor
Cold aisle sensor
Hot aisle sensor
Outdoor intake air
sensor 3
Cold aisle
temperature and
humidity sharing
Hot aisle temperature
and humidity sharing
Supply air damper
Copyright © Huawei Digital Power Technologies Co., Ltd.
7 Power-On Commissioning
Description
Enables or disables a sensor.
Enables or disables a sensor.
Enables or disables a sensor.
Enables or disables a sensor.
Enables or disables a sensor.
This function can be enabled only
when at least one smart cooling
product in the teamwork group is
equipped with cold aisle T/H sensors. If
this function is enabled, the master
unit in the teamwork group collects
the cold aisle temperature and
humidity values from all units
equipped with cold aisle sensors, and
synchronizes the temperature and
humidity control type and setpoints to
all slave units.
This function can be enabled only
when at least one smart cooling
product in the group is equipped with
hot aisle T/H sensors. If this function is
enabled, the master unit in the
teamwork group collects the hot aisle
temperature and humidity values from
all units equipped with hot aisle
sensors, and synchronizes the
temperature and humidity control type
and setpoints to all slave units.
● Disable: The air damper function of
the unit is disabled.
● AO Ctrl: Select AO Ctrl for AO-type
air dampers.
104