FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
----End
12.15.5 Charging the Remaining Refrigerant
Prerequisites
●
●
●
Procedure
Step 1 Tap Start on the home screen.
Step 2 Choose Maint > Diagnostic > Enter to enter the diagnostic mode.
Step 3 Change the compressor rotational speed to 3000 rpm.
Step 4 Open the low pressure valve of the pressure gauge, and charge the remaining
refrigerant from the low pressure needle valve in small flow or intermittently.
Figure 12-37 Charging the remaining refrigerant
(1) Refrigerant cylinder
(4) Connection nut
Charge refrigerant on the basis of the precharging.
Issue 03 (2021-04-20)
NO TE
Tighten the needle valve bonnets when the charge is complete. Check whether a needle
valve leaks by applying soap bubbles to the valve vent or using a halogen leak detector. If
leakage occurs, contact technical support engineers.
Before starting the compressor, ensure that the unit switch is turned on.
Remove the refrigerant cylinder after ensuring that no more refrigerant needs
to be charged.
Charge refrigerant in an amount exactly as standard charge required.
Otherwise, the unit may be damaged.
NO TICE
Copyright © Huawei Digital Power Technologies Co., Ltd.
(2) Electronic balance
(5) Low pressure needle valve
12 Component Replacement
(3) Pressure gauge
186