FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Procedure
Step 1 On the home screen of the display module, tap Shutdown and turn off the unit
switch in the PDF.
Exercise caution because the unit is still energized after it is shut down on the
home screen of the display module.
Step 2 Remove the outdoor intake air filter.
Step 3 Remove the indoor return air T/H sensor. Cut off the cable tie that secures the
cable, remove the screws from the sheet metal fastener of the T/H sensor, push
the baffle plate, and remove the T/H sensor and the sheet metal fastener.
Figure 12-13 Removing the T/H sensor sheet metal
Figure 12-14 Removing a T/H sensor