3
I/O MODULES REPLACEMENT
3

3.1 Alternative I/O Module Models List

A0J2H models to be discontinued
Product name
Input module
3
- 1
I/O MODULES REPLACEMENT
3
Model name
Model name
*1
QX10
A0J2-E32A
*1
QX40
A0J2-E32D
Alternative Q series models
Remarks (restrictions)
1) Change in external wiring: Required
2) Change in the number of modules: Required
(2 modules necessary)
3) Change in a program
Change in the number of occupied I/O points: Required (64
points  16 points × 2)
4) Change in specifications
Change in rated input voltage: Not required
Change in rated input current: Required (Approx. 10mA 
Approx. 8mA)
Change in ON voltage/ON current: Required
Change in OFF voltage/OFF current: Required
Change in input resistance: Required
5) Change in functions: Not required
1) Change in external wiring: Required
2) Change in the number of modules: Required
(2 modules necessary)
3) Change in a program
Change in the number of occupied I/O points: Required (64
points  16 points × 2)
4) Change in specifications
Change in rated input voltage: Required (12VDC not
*2
applicable)
Change in rated input current: Required (Approx. 7mA 
Approx. 4mA)
Change in ON voltage/ON current: Required
Change in OFF voltage/OFF current: Required
Change in input resistance: Required
5) Change in functions: Not required