7
PROGRAMS REPLACEMENT

7.3 Precautions for Parameter Replacement

This section explains the conversion of the parameter when replacing the A0J2HCPU program with
QCPU.
<Compatibility>
: Common items of the A0J2HCPU and QCPU, and converted without any changes.
: Items that needs resetting after conversion due to partial differences in functions/specifications.
× : Items to be deleted because there are no common items between the A0J2HCPU and QCPU.
Confirm the contents after conversions, and correct/reset if necessary.
Name
Sequence program capacity
Microcomputer program
capacity
Comment capacity
File register capacity
WDT settings
Operation mode during errors
RUN-PAUSE contact
STOP  RUN output mode
Interrupt counter settings
I/O assignment
Number of device points
Latch relay (L)
Data register (D)
Link relay (B)
Link register (W)
Low speed timer (T)
High-speed timer (T)
Retentive timer (ST)
Counter (C)
MELSECNET(II), /B
Compatibility
No attention is required to the program capacity.
×
A microcomputer program is not available.
No attention is required to the comment capacity.
Resetting is necessary as the specifications differ.
Becomes the default value (200ms).
Becomes default (stop all).
Resetting is necessary.
Becomes default (output before STOP).
Resetting is necessary.
Resetting is necessary as the specifications differ.
Becomes the number of default points.
As the number of default points exceeds the number of
A0J2HCPU points, program correction is unnecessary.
M and L are separate devices.
"L" on the program is converted just as "L".
Converted as a single device.
As the latch range is the entire range from the minimum device
number to the maximum device number, it must be reviewed.
The parameter is deleted as it is not compatible with
×
MELSECNET(II), /B.
Remarks
7
- 25