3
I/O MODULES REPLACEMENT
Specifications
Fuse rating
Fuse blown indication
Protection function
Protection function reset
Common terminal
arrangement
Operation indication
Specifications
Current consumption
External connection
method
Applicable wire size
Applicable solderless
terminal
External dimensions
Weight
*1
Use the QX70 when using 12VDC.
*2
Check the specifications of the sensor or switches to be connected to the QX80.
*3
The fuse blown is not detected when the external power supply is off.
A0J2E-E28DT output
specifications
Available (When a fuse blown
occurs, LED is lit, and a signal is
Available (overheat protection
and short circuit protection)
Overheat protection: activated to
two points
Automatic reset
(by deactivating overheat
protection function)
8 points/common
(Common terminal: TB26)
4 points/common
(Common terminal: TB32)
Available (Turning ON the output
turns LED ON)
A0J2E-E56DT
0.125A (TYP. All points are ON.)
36-point terminal block
connector
(M3 × 6 screws)
2
0.75 to 2mm
1.25-3, 1.25-YS3A,
2-S3, 2-YS3A,
(Sleeved solderless terminals
V1.25-3, V1.25-YS3A,
V2-S3, V2-YS3A
250(H) × 132(W) × 41(D)mm
98(H) × 27.4(W) × 90(D)mm × 2
0.68kg
: Compatible,
QY80
Compatibility
6.7A (Not exchangeable)
(Fuse blown capacity: 50A)
*3
output to the CPU)
16 points/common
(Common terminal: TB17)
ON indication (LED)
QX80/QY80
Compatibility
0.05 + 0.08 = 0.13A
(TYP. All points are ON.)
18-point terminal block
(M3 × 6 screws)
1 piece/module
2
0.3 to 0.75mm
core
(Outside diameter: 2.8mm or
less)
R1.25-3
cannot be used.)
0.16 + 0.17 = 0.33kg
: Partially changed, × : Incompatible
Precautions for replacement
The QY80 has the fuse instead of
overheat and short circuit
protection function.
As the common changes from two
commons to a common, wiring with
a different voltage for each
common is not possible.
Precautions for replacement
Review current capacity since
current consumption is increased.
×
×
Wiring change is required.
×
×