Mitsubishi Electric MELSEC-A0J2H Series Handbook page 206

Table of Contents

Advertisement

(5) Specifications comparison between A0J2-E24S and interface module (SC-A0JQIF24S)
Specifications
A0J2-E24S output specifications
Number of output points
Insulation method
Rated switching voltage
Maximum switching
voltage
Maximum switching
current
Minimum switching
24VAC100mA, 100V/240VAC10mA
voltage/current
Maximum inrush current
Leakage current at off
Maximum voltage drop
at on
Temperature derating
OFFON
Response
time
ONOFF
Fuse rating
Fuse blown indication
(LED turns on by fuse blown, and a
signal is output to the CPU module.)
CR
Surge
absorber
suppressor
Varistor
Common terminal
arrangement
(Common terminal: TB9, TB19, TB29)
Operation indication
(Turning ON the input turns LED ON)
Specifications
5VDC internal current
consumption
External
Voltage
supply
power
(Module
power
Current
supply)
External connection
36-point terminal block connector
method
Applicable wire size
(Applicable tightening torque 69N•cm)
Applicable solderless
terminal
Weight
External dimensions
App
- 11
24 points
Photocoupler
100 to 240VAC, 40-70Hz
264AAC
0.6A/point, 2.4A/common
20A10ms or less
8A100ms or less
1.5mA (120VAC60Hz)
3mA (240VAC60Hz)
1.5V or less (0.1A-0.6A)
1.8V or less (0.1A or less)
2.0V or less (10-50mA)
None
1ms or less (6ms TYP.)
0.5 cycle + 1ms or less
Fast blow fuse 3.2A
(1/common) HP-32
Available
0.022µF+47
None
8 points/common
Available
A0J2-E24S
400mA (TYP. All points are ON.)
None
None
(M3 × 6 screws)
2
0.75 to 2mm
1.25-3, 1.25-YS3A, 2-S3,
2-YS3A, V1.25-3, V1.25-YS3A,
V2-S3, V2-YS3A
0.70kg
250(H) × 132(W) × 41(D) mm
SC-A0JQIF24S output
specifications
24 points
Photocoupler
100 to 240VAC, 47-63Hz
264VAC
0.6A/point, 2.4A/common
24VAC100mA,100V/240VAC10mA
20A10ms or less
8A100ms or less
1.5mA (120VAC60Hz)
3mA (240VAC60Hz)
1.5V or less (0.1A-0.6A)
1.8V or less (0.1A or less)
2.0V or less (10-50mA)
*1
Refer to temperature derating chart
1ms or less (1ms TYP.)
0.5 cycle + 1ms or less
None
None
0.015µF+22
Varistor (400 to 540V)
8 points/common
(Common terminal: TB9, TB19, TB29)
None
SC-A0JQIF24S
24VDC ±10%
Ripple voltage 4Vp-p or less
370mA
36-point terminal block connector
(M3 × 6 screws)
2
0.75 to 2mm
(Applicable tightening torque 69N•cm)
1.25-3, 1.25-YS3A, 2-S3,
2-YS3A, V1.25-3, V1.25-YS3A,
V2-S3, V2-YS3A
0.46kg
*4
182(H) × 132(W) × 41(D)mm
: Compatible,
: Partially changed, × : Incompatible
Compatibility
Precautions for replacement
The maximum frequency of SC-
A0JQIF24S is smaller than the one of
A0J2-E24S.
Use it within the range shown in the
temperature derating chart.
In combination with Q series output
module:
*2
2ms or less
In combination with Q series output
module:
0.5 cycle + 2ms or less.
Install one fuse per common externally.
×
(A fuse and fuse holder are included.)
×
Operation indication can be checked
with Q series input module.
Compatibility
Precautions for replacement
To deliver a power for programmable
controller operation, connecting a
×
module power supply to the interface
module, TB35 or TB36 is required.
If the voltage exceeds existing power
×
capacity, add 24VDC power supply
separately.
Also consider the weight of fixed stand
of programmable controller.
Check the dimensions since they
×
depend on the installation type
(building-up/horizontal/separate type).
*2
*3

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec q series

Table of Contents