I/O MODULES REPLACEMENT
(4) Specifications comparison between A0J2-E24T and QY50
Specifications
Number of output points
Insulation method
Rated load voltage
Operating load voltage
range
Maximum load current
Maximum inrush current
Leakage current at OFF
Maximum voltage drop at
ON
OFFON
Response
time
ONOFF
Surge suppressor
Common terminal
arrangement
Operation indication
Fuse
Fuse blown indication
External connection
method
Applicable wire size
Applicable solderless
terminal
Voltage
External
supply
power
Current
Current consumption
External dimensions
Weight
A0J2-E24T
24 points
Photocoupler
12VDC/24VDC
10.2 to 30VDC
0.5A/point, 4A/common
4A, 10ms or less
0.1mA or less
0.9VDC (TYP.) 0.5A
1.5VDC (MAX.) 0.5A
2ms or less
2ms or less (Resistance load)
Varistor (52 to 62V)
8 points/common
(Common terminal: TB9, TB19,
TB29)
Available (Turning ON the output
turns LED ON)
None
Available (When a fuse blown
None
occurs, LED is lit, and a signal is
36-point terminal block
connector
(M3 × 6 screws)
2
0.75 to 2mm
1.25-3, 1.25-YS3A,
2-S3, 2-YS3A,
(Sleeved solderless terminals
V1.25-3, V1.25-YS3A,
V2-S3, V2-YS3A
12VDC/24VDC
(10.2 to 30VDC)
23mA
(TYP. 24VDC/8 points/common
ON)
0.145A (TYP. All points are ON.)
0.08A (TYP. All points are ON.)
250(H) × 132(W) × 41(D) mm
0.68kg
: Compatible,
QY50
Compatibility
16 points
Photocoupler
12VDC/24VDC
10.2 to 28.8VDC
0.5A/point, 4A/common
4A, 10ms or less
0.1mA or less
0.2VDC (TYP.) 0.5A
0.3VDC (MAX.) 0.5A
1ms or less
1ms or less
(Rated load, resistance load)
Zener diode
16 points/common
(Common terminal: TB18)
ON indication (LED)
6.7A (Not exchangeable)
(Fuse blown capacity: 50A)
output to the CPU)
18-point terminal block
(M3 × 6 screws)
2
0.3 to 0.75mm
core
(Outside diameter: 2.8mm or
less)
R1.25-3
cannot be used.)
12VDC/24VDC
(10.2VDC to 28.8VDC)
(Ripple ratio within 5%)
20mA (During 24VDC)
98(H) × 27.4(W) × 90(D) mm
0.17kg
: Partially changed, × : Incompatible
Precautions for replacement
When seventeen or more points
are used, use two QY50 modules.
Voltages exceeding 28.8VDC
cannot be applied.
Use caution on the used current of
the entire module.
As the common changes from
three commons to a common,
wiring with a different voltage for
each common is not possible.
×
×
Wiring change is required.
×
Voltages exceeding 28.8 VDC
cannot be applied.
×
The dimensions are different.
3
- 20