Advertisement

3
I/O MODULES REPLACEMENT
(8) Specifications comparison between A0J2-E56AR and QX10+QY10
Specifications
Number of input points
Insulation method
Rated input voltage
Input voltage distortion
Rated input current
Operating voltage range
Maximum number of
simultaneous input
points
ON voltage/ON current
OFF voltage/OFF current
Inrush current
Input impedance
OFFON
Response
time
ONOFF
Common terminal
arrangement
Operation indication
Specifications
Number of output points
Insulation method
Rated switching voltage/
current
Minimum switching load
Maximum switching
voltage
Maximum switching
frequency
3
- 37
A0J2-E56AR input
specifications
32 points
Photocoupler
100-120VAC, 50/60Hz
Approx. 8mA (100VAC, 60Hz)
10mA (100VAC, 60Hz)
Approx. 7mA (100VAC, 50Hz)
85 to 132VAC
(50/60Hz±5%)
60% (10 points/common)
simultaneously ON
80VAC or more/6mA or more
40VAC or less/4mA or less
Max. 300mA, within 0.3ms
(132VAC)
Approx. 10k (60Hz),
Approx. 12k (50Hz)
15ms or less (6ms TYP.)
35ms or less (16ms TYP.)
16 points/common
(Common Terminal: TB17, TB34)
Available (Turning ON the input
turns LED ON)
A0J2-E56AR output
specifications
24 points
Photocoupler
24VDC 2A (Resistance load)/
24VDC 2A (Resistance load)/
point
240VAC 2A (COS=1)/point
5A/common
5VDC 1mA
264VAC, 125VDC
3600 times/hr
: Compatible,
QX10
Compatibility
16 points
Photocoupler
100-120VAC, 50/60Hz
Within 5%
85 to 132VAC
(50/60Hz±3Hz)
*2
Refer to the derating chart.
80VAC or more/5mA or more
(50Hz, 60Hz)
30VAC or less/1.7mA or less
(50Hz, 60Hz)
Max. 200mA, within 1ms
(with 132VAC)
Approx. 12k (60Hz),
Approx. 15k (50Hz)
15ms or less
(100VAC 50Hz, 60Hz)
20ms or less
(100VAC 50Hz, 60Hz)
16 points/common
(Common terminal: TB17)
ON indication (LED)
QY10
Compatibility
16 points
Relay
point
240VAC 2A (COS = 1)/point
8A/common
5VDC 1mA
264VAC, 125VDC
3600 times/hr
: Partially changed, × : Incompatible
Precautions for replacement
When seventeen or more points
are used, use two QX10s.
Rated input current is smaller.
Use it within the range shown in the
derating chart.
*1
OFF current is smaller.
*1
Input impedance is larger.
Precautions for replacement
When seventeen or more points
are used, use two QY10 modules.
Although the insulation methods
differ, the performance of the
insulation is the same.