(1) Specifications comparison between A0J2-E28DR and QX40+QY10
Specifications
Number of input points
Insulation method
Rated input voltage
Rated input current
Operating voltage range
Maximum number of
simultaneous input
points
ON voltage/ON current
OFF voltage/OFF current
Input resistance
Input form
OFFON
Response
time
ONOFF
Common terminal
arrangement
Operation indication
Specifications
Number of output points
Insulation method
Rated switching voltage/
current
Minimum switching load
Maximum switching
voltage
Maximum switching
frequency
*1
Use the QX70 when using 12VDC.
*2
Check the specifications of the sensor or switches to be connected to the QX40.
A0J2-E28DR input
specifications
16 points
Photocoupler
12VDC/24VDC
Approx. 3mA/Approx. 7mA
10.2 to 26.4VDC
(Ripple ratio within 5%)
100% (16 points)
simultaneously ON
9.5VDC or more/2.6mA or more
19VDC or more/3mA or more
6VDC or less/1.0mA or less
11VDC or less/1.7mA or less
Approx. 3.4k
Sink input
(Input current flows off.)
1ms/5ms/10ms/20ms/70ms or
10ms or less (6ms TYP.)
(Set it with CPU parameter.)
1ms/5ms/10ms/20ms/70ms or
10ms or less (7.5ms TYP.)
(Set it with CPU parameter.)
16 points/common
(Common terminal: TB17)
Available (Turning ON the input
turns LED ON)
A0J2-E28DR output
specifications
12 points
Photocoupler
24VDC 2A (Resistance load)/
24VDC 2A (Resistance load)/
point
240VAC 2A (COS=1)/ point
240VAC 2A (COS = 1)/ point
5A/common
5VDC 1mA
264VAC, 125VDC
3600 times/hr
: Compatible,
QX40
Compatibility
16 points
Photocoupler
24VDC
Approx. 4mA
20.4 to 28.8VDC
(Ripple ratio within 5%)
100% simultaneously ON
Approx. 5.6k
Positive common
less
Initial setting is 10ms.
less
Initial setting is 10ms.
16 points/common
(Common terminal: TB17)
ON indication (LED)
QY10
Compatibility
16 points
Relay
point
8A/common
5VDC 1mA
264VAC, 125VDC
3600 times/hr
: Partially changed, × :Incompatible
Precautions for replacement
*1
12VDC cannot be used.
*2
Rated input current is smaller.
*1
12VDC cannot be used.
*1
12VDC cannot be used.
*1
12VDC cannot be used.
*2
Input resistance is greater.
The name is different, but the
specificaton is equal.
Input response time of the
parameter must be used at the
initial value (10ms).
Precautions for replacement
Although the insulation methods
differ, the performance of the
insulation is the same.