Mitsubishi Electric MELSEC-A0J2H Series Handbook page 94

Table of Contents

Advertisement

3
I/O MODULES REPLACEMENT
(15)Specifications comparison between A0J2E-E28DT and QX80+QY80
Specifications
Number of input points
Insulation method
Rated input voltage
Rated input current
Operating voltage range
Maximum number of
simultaneous input
points
ON voltage/ON current
OFF voltage/OFF current
Input resistance
Input format
OFFON
Response
time
ONOFF
Response
OFFON
time high-
speed
mode (Only
upper 8
ONOFF
points)
Common terminal
arrangement
Operation indication
Specifications
Number of output points
Insulation method
Rated load voltage
Operating load voltage
range
Maximum load current
Maximum inrush current
Leakage current at OFF
Maximum voltage drop at
ON
OFFON
Response
time
ONOFF
Voltage
External
supply
power
Current
Surge suppressor
3
- 53
A0J2E-E28DT input
specifications
16 points
Photocoupler
12VDC/24VDC
3mA/7mA
10.2 to 26.4VDC
(Ripple ratio within 5%)
100% simultaneously ON
9.5VDC or more/2.6mA or more
19VDC or more/3mA or more
6VDC or less/1.0mA or less
11VDC or less/1.7mA or less
Approx. 3.4k
Source input
(Input current flows in.)
1ms/5ms/10ms/20ms/70ms or
5.5ms or less (TYP.)
(Set it with CPU parameter.)
1ms/5ms/10ms/20ms/70ms or
6.0ms or less (TYP.)
(Set it with CPU parameter.)
1ms/5ms/10ms/20ms/70ms or
0.5ms or less
(Set it with CPU parameter.)
1ms/5ms/10ms/20ms/70ms or
1.0ms or less
(Set it with CPU parameter.)
16 points/common
(Common terminal: TB17)
Available (Turning ON the input
turns LED ON)
A0J2E-E28DT output
specifications
12 points
Photocoupler
12/24VDC
10.2 to 26.4VDC
0.8A/1 point, 0.7A/1 point
(60% ON, 55°C)
No restriction (Short protect)
1.0mA or less
1.0V (TYP.) 0.8A,
1.5V (MAX.) 0.8A
0.5ms or less
1.5ms or less
(Rated load, resistance load)
12/24VDC
(10.2 to 30VDC)
100mA
(24VDC, All points are ON.)
Surge absorbing diode
: Compatible,
QX80
Compatibility
16 points
Photocoupler
24VDC
Approx. 4mA
20.4 to 28.8VDC
(Ripple ratio within 5%)
100% simultaneously ON
Approx. 5.6k
Negative common
less
Initial setting is 10ms.
less
Initial setting is 10ms.
less
Initial setting is 10ms.
less
Initial setting is 10ms.
16 points/common
(Common terminal: TB18)
ON indication (LED)
QY80
Compatibility
16 points
Photocoupler
12 to 24VDC
10.2 to 28.8VDC
0.5A/1 point, 4A/1 common
4A 10ms or less
0.1mA or less
0.2VDC (TYP.) 0.5A,
0.3VDC (MAX.) 0.5A
1ms or less
1ms or less
12 to 24VDC (+20/-15%)
(Ripple ratio within 5%)
20mA (During 24VDC)
Zener diode
: Partially changed, × : Incompatible
Precautions for replacement
*1
12VDC cannot be used.
*2
Rated input current is smaller.
*1
12VDC cannot be used.
*1
12VDC cannot be used.
*1
12VDC cannot be used.
*2
Input resistance is greater.
The name is different, but the
specificaton is equal.
Set the input response time of the
parameter to 5ms before use.
Set the input response time of the
parameter to 1ms before use.
Precautions for replacement
The maximum load current per
point is smaller. Use caution on
selecting the load to use.
The inrush current value differs.
Use caution on selecting the load
to use.
The response times differ.
Voltages exceeding 28.8VDC
cannot be applied.

Advertisement