FusionDC1000A Prefabricated All-in-One Data
Center
Maintenance Guide (IT Scenario)
Item
Method
Cable
Check that no cable has
aged.
Temperat
Check and calibrate the
ure and
T/H sensor.
humidity
(T/H)
sensor
Water
Check whether the water
detector
detector cable is securely
connected.

3.6.3 Monitoring System

Table 3-16 Semi-annual maintenance checklist for the monitoring system
Check Item
Operation
Smart ETH
Power input
gateway
Power output
PWR indicator
Issue 01 (2021-04-20)
Check Standard
Cables are not aged.
The T/H sensors are
working properly,
and the
temperature and
humidity deviations
are within the
allowed range.
The water sensor
cable is securely
connected.
Check Standard
Input voltage: 45–55 V DC
Output voltage: 45–55 V DC
Steady on: The power supply is
normal.
Off: No power supply is
available.
Copyright © Huawei Technologies Co., Ltd.
3 Routine Maintenance
Troubleshooting
Replace aged cables.
If the temperature error is greater
than 1°C or humidity error is
greater than 5%, the T/H sensor
must be calibrated or replaced.
For the calibration method, see
the ACC Precision Air Conditioner
Controller User Manual.
Connect the cable properly.
Troubleshooting
Check the input power cables
if the input voltage is
abnormal.
For details, contact Huawei
technical support.
Check the input power cables.