Figure 4-38 Removing a water pump assembly
Step 8 Use a flat-head screwdriver to remove the hose clamp from the water pump, and
then remove the pump, as shown in by (1) and (2) in
Figure 4-39 Removing a water pump
Step 9 Install a new water pump and reinstall the water pump assembly in the cabinet,
as shown in by (3) in
hose clamp. Connect the water pump power cable.
Step 10 Remove the blockage from the water pan, reinstall the water pan cover, and then
close the front door.
----End