Huawei FusionDC1000A Maintenance Manual page 38

Prefabricated all-in-one data center
Hide thumbs Also See for FusionDC1000A:
Table of Contents

Advertisement

FusionDC1000A Prefabricated All-in-One Data
Center
Maintenance Guide (IT Scenario)
Check Item
Content
RF_Z indicator
AC actuator
Power input
Power output
PWR indicator
ALM indicator
Issue 01 (2021-04-20)
Check Standard
On: No network parameters
exist. A network is waiting to
be created.
Blinking slowly: A network is
set up, and node access is not
allowed (the indicator blinks at
0.5 Hz, on for 1s and then off
for 1s)
Blinking at super short
intervals: A network is set up,
and node access is allowed (the
indicator blinks at 10 Hz, on for
0.05s and then off for 0.05s).
Blinking at super short intervals
intermittently: The device is
searching for a network (the
indicator blinks at 2 Hz, on for
0.5s and then off for 0.5s).
Input voltage: 90–240 V AC
Output voltage: 90–240 V AC
Steady on: The power supply is
normal.
Off: No power supply is
available.
Steady on: A fault alarm is
generated.
Off: No fault alarm is
generated.
Copyright © Huawei Technologies Co., Ltd.
3 Routine Maintenance
Troubleshooting
See the ECC800-Pro
documents.
Check the input power cables
if the input voltage is
abnormal.
For details, contact Huawei
technical support.
Check the input power cables.
Clear alarms by referring to
the ECC800-Pro documents.