Figure 4-22 Removing a differential pressure switch
Step 4 Use a Phillips screwdriver to remove the screws on the top cover of the differential
pressure switch and cable screws, as shown by (2) in
cables.
Step 5 Use a Phillips screwdriver to remove the three screws, and remove the differential
pressure switch, as shown by (3) in
Step 6 Set the new differential pressure switch to 250 Pa.
Figure 4-23 Setting values for a differential pressure switch