Context
Components and working principle: A liquid level detector is composed of the
conductor outer jacket, liquid level detector, switch, and card pole. A liquid level
detector rises or drops as the liquid level changes due to the magnetism of the
liquid level switch, causing the reed switch chip in the specified position inside the
sensor detection pipe to move and send the contact on/off conversion signal to
control the liquid level detector.
The liquid level detector can be maintained only from the front.
Figure 4-30 Liquid level detector
(1) High liquid level detector
Procedure
Step 1 Tap Shutdown on the LCD home screen.
Exercise caution because the NetCol5000-A is still energized when it is being shut
down over the LCD.
Step 2 Open the front door and remove the four screws that secure the water pan cover.
Figure 4-31 Removing a water pan cover
Issue 01 (2021-04-20)
A spare liquid level detector of the same model is available and functional.
Tool: Phillips screwdriver
NO TICE
Copyright © Huawei Technologies Co., Ltd.
(2) Low liquid level detector
4 Parts Replacement