Huawei FusionDC1000A Maintenance Manual page 54

Prefabricated all-in-one data center
Hide thumbs Also See for FusionDC1000A:
Table of Contents

Advertisement

FusionDC1000A Prefabricated All-in-One Data
Center
Maintenance Guide (IT Scenario)
Device
Method
Fire alarm
When both the heat
horn/strobe
detector and smoke
detector generate an
alarm, the fire alarm
horn/strobe generates a
harsh sound.
ASD
Check the ASD sampling
pipes.
Remove or block a
sampling pipe.
Release smoke to the
furthest end of an ASD
sampling pipe.
Check the ASD operation
panel.
Check whether the
backup power is working
properly, and whether
the VESDA restarts
normally after the mains
power is disconnected.
ASD power
Check the power
supply
indicator.
Issue 01 (2021-04-20)
Check Standard
The fire alarm horn/strobe
generates glaring flashes and
shrill alarms.
The supports and connectors of
the sampling pipes are securely
connected.
An alarm is generated.
The ASD generates an alarm in
120s.
The ASD sends an alarm signal
to the host.
All indicators are normal.
The backup power is working
properly, and the VESDA
restarts normally after the
mains power is disconnected.
The power indicator turns on.
Copyright © Huawei Technologies Co., Ltd.
3 Routine Maintenance
Troubleshooting
1. Check cables
connected to the
fire alarm horn/
strobe. If a short
circuit or open
circuit is
identified,
reconnect the
cables.
2. If the fire alarm
horn/strobe does
not react, replace
it.
Replace damaged
sampling pipes, and
apply glue where
pipes are not well
sealed.
See documents
delivered with the
ASD.
See documents
delivered with the
ASD.
See documents
delivered with the
ASD.
See documents
delivered with the
ASD.
See documents
delivered with the
ASD.
1. Check the power
cables.
2. Replace the
battery for the
ASD power box.
46