Step 5 Remove the front and rear sealing plates from the smart cooling product base.
Figure 4-4 Removing sealing plates from the smart cooling product base
Step 6 Reinstall the removed ESD floors.
● The ventilation floor panel of the hot aisle can be reinstalled after the water
refill and drainage pipes of the smart cooling product are removed.
● Adjust the height of the floor tray to ensure that the reinstalled floor panels are
flush with other floor panels.
Step 7 Remove fasteners at the top and bottom of the smart cooling product.
Issue 01 (2021-04-20)
NO TICE
Copyright © Huawei Technologies Co., Ltd.
4 Parts Replacement
61