Huawei FusionDC1000A Maintenance Manual page 82

Prefabricated all-in-one data center
Hide thumbs Also See for FusionDC1000A:
Table of Contents

Advertisement

FusionDC1000A Prefabricated All-in-One Data
Center
Maintenance Guide (IT Scenario)
Procedure
Step 1 Tap Shutdown on the controller home screen.
Exercise caution because the equipment is still energized after it is shut down on
the controller home screen.
Step 2 Remove the cable terminal from the RS485 port on the T/H sensor.
Step 3 Pull out the T/H sensor.
Before installing the new T/H sensor, check that its DIP switch settings are consistent with the
DIP switch settings of the old T/H sensor.
Step 4 Connect the RS485 cable terminal and install the new T/H sensor in the correct
position.
Step 5 Set the DIP switch on the T/H sensor.
Table 4-3 DIP switch settings on T/H sensors
Locati
on
Air
return
side
Cold
aisle
Hot
aisle
----End
Issue 01 (2021-04-20)
NO TICE
NO TE
Display Name
Return air 2
temp/humid
Cold aisle 1
temp/humid
Cold aisle 2
temp/humid
Cold aisle 3
temp/humid
Hot aisle 1
temp/humid
Hot aisle 2
temp/humid
Hot aisle 3
temp/humid
Copyright © Huawei Technologies Co., Ltd.
Addr
DIP Switch No.
ess
1
2
1
ON
OFF
11
ON
ON
12
OFF
OFF
13
ON
OFF
21
ON
OFF
22
OFF
ON
23
ON
ON
4 Parts Replacement
3
4
5
OFF
OFF
OFF
OFF
ON
OFF
ON
ON
OFF
ON
ON
OFF
ON
OFF
ON
ON
OFF
ON
ON
OFF
ON
6
OFF
OFF
OFF
OFF
OFF
OFF
OFF
74