Replacing The Indoor Fan - Huawei FusionDC1000A Maintenance Manual

Prefabricated all-in-one data center
Hide thumbs Also See for FusionDC1000A:
Table of Contents

Advertisement

FusionDC1000A Prefabricated All-in-One Data
Center
Maintenance Guide (IT Scenario)
Figure 4-18 Removing an air filter
Step 2 Install air filters in accordance with the arrow direction shown on the air filter
frame (the arrow points to the smart cooling product interior). Then close the rear
door.
----End
Follow-up Procedure
Power on the NetCol5000-A, choose Maint > Performance Maint on the home
screen, and clear the air filter runtime.

4.2.2.4 Replacing the Indoor Fan

Prerequisites
Context
The indoor fan can be maintained only from the front.
Procedure
Step 1 On the controller home screen, tap Shutdown, and turn off the smart cooling
product switch in the upstream PDC.
Step 2 Open the front door and turn off the switch for the faulty fan.
Issue 01 (2021-04-20)
The indoor fan needs to be replaced.
A spare indoor fan of the same model is available and functional.
Tools: protective gloves, Phillips screwdriver, diagonal pliers, cable ties.