Fire Extinguishing System (Ce) - Huawei FusionDC1000A Maintenance Manual

Prefabricated all-in-one data center
Hide thumbs Also See for FusionDC1000A:
Table of Contents

Advertisement

FusionDC1000A Prefabricated All-in-One Data
Center
Maintenance Guide (IT Scenario)
Device
Method
Hand-held
Check the fire
fire
extinguisher.
extinguisher
Fire control
Check cables
cable
connected to the
electromagnetic
valve and pressure
announciator.
Emergency
Check the emergency
start/abort
start/abort switch.
switch

3.5.4 Fire Extinguishing System (CE)

Table 3-12 Quarterly maintenance checklist for the fire extinguishing system
Device
Method
Extinguishant
1. Switch off the power
control panel
input circuit breaker of
batteries
the fire alarm control
panel so that the
batteries power the
panel.
2. Measure the battery
voltage using a
multimeter.
Hand-held
Check the hand-held fire
fire
extinguisher.
extinguisher
Issue 01 (2021-04-20)
Check Standard
The fire
extinguisher is
intact.
The pressure
pointer of the
fire extinguisher
is in the green
zone.
The fire
extinguisher is
within the
validity period.
Cables are
securely
connected to the
electromagnetic
valve and
pressure
announciator.
The exterior and
key panel are
intact. The run
indicator is
steady green.
Check Standard
1. The extinguishant
control panel reports
a power supply fault.
2. The battery voltage is
24±1 V DC.
The hand-held fire
extinguisher is in good
condition.
Copyright © Huawei Technologies Co., Ltd.
3 Routine Maintenance
Troubleshooting
Replace the fire extinguisher.
Replace the fire extinguisher.
Replace the fire extinguisher.
Connect the cable properly.
If the exterior is damaged, replace the
emergency start/abort switch.
Maintenance Guide
Replace the extinguishant
control panel batteries.
Replace the hand-held
fire extinguisher.