Other Systems - Huawei FusionDC1000A Maintenance Manual

Prefabricated all-in-one data center
Hide thumbs Also See for FusionDC1000A:
Table of Contents

Advertisement

FusionDC1000A Prefabricated All-in-One Data
Center
Maintenance Guide (IT Scenario)
Device
Method
Smoke
Check the smoke
detector
detector indicator.
Heat
Check the heat
detector
detector indicator.
SmartLi
Operating
environment
Appearance
Pressure gauge for
fire detection and
fire extinguishing
equipment

3.4.6 Other Systems

Table 3-8 Monthly maintenance checklist for other systems
Item
Method
Pre-fab.
Check the pre-fab.
module
module exterior for
repainting
damage or corrosion.
External
Check whether
environment
hazards or potential
of pre-fab.
hazards exist around
modules
the pre-fab. modules.
Check whether
obvious rubbish
exists around the
pre-fab. modules.
Issue 01 (2021-04-20)
Check Standard
The indicator blinks
once every 6s.
The indicator blinks
once every 6s.
There is no heat
source or direct
sunlight nearby.
No damage, leakage,
or deformation is
found.
The pressure gauge
pointer is in the green
zone.
Check Standard
The pre-fab. module and
bases are free from paint
flake-off, rust, or corrosion.
No hazard or potential
hazard exists around the
pre-fab. modules.
No obvious rubbish exists
around the pre-fab.
modules.
Copyright © Huawei Technologies Co., Ltd.
3 Routine Maintenance
Maintenance Guide
Replace the smoke detector.
Replace the heat detector.
Check that batteries are far away
from heat sources and are not
exposed to direct sunlight.
Disconnect the faulty battery
module, take photos, and replace
it with a new one..
If the pressure gauge pointer is in
the red zone, contact Huawei
technical support.
Troubleshooting
Maintain or replace the
rusty or damaged part of
the pre-fab. modules.
Repaint areas with paint
flake-off or rust.
Take measures to handle
potential hazards.
Clean the rubbish.