3.18 Adv Parameter Data Set

3.19 LC-## Logic Controller

Parameter group related to programming the drive's built-in Logic Controller. The Logic Controller consists of a series of user defined actions (see par. LC-53) that
are executed when the corresponding user-defined events are met.
3.19.1 LC-0# LC Settings
Parameters to configure the activation, deactivations and reset of the Logic Controller (LC).
LC-00 Logic Controller Mode
Option:
[0] *
Off
[1]
On
LC-01 Start Event
Option:
[0] *
False
[1]
True
[2]
Running
[3]
In range
[4]
On reference
[5]
Torque limit
[6]
Current Limit
[7]
Out of current range
[8]
Below I low
[9]
Above I high
[10]
Out of speed range
[11]
Below speed low
[12]
Above speed high
[13]
Out of feedb. range
[14]
Below feedb. low
[15]
Above feedb. high
[16]
Thermal warning
[17]
Line voltage out of range
[18]
Reversing
Function:
Disables the Logic Controller.
Enables the Logic Controller.
Function:
Select the boolean (TRUE or FALSE) input to activate Logic Controller.
False [0] enters the fixed value - FALSE
True [1] enters the fixed value - TRUE.
Running [2] The motor is running.
In range [3] The motor is running within the programmed current and speed ranges set in par.
H-70 Warning Current Low to par. H-73 Warning Speed High.
On reference [4] The motor is running on reference.
Torque limit [5] The torque limit, set in par. F-40 Torque Limiter (Driving) or par. F-41 Torque Limiter (Brak-
ing), has been exceeded.
Current limit [6] The motor current limit, set in par. F-43 Current Limit, has been exceeded.
Out of current range [7] The motor current is outside the range set in par. F-43 Current Limit.
Below I low [8] The motor current is lower than set in par. H-70 Warning Current Low.
Above I high [9] The motor current is higher than set in par. H-71 Warning Current High.
Out of speed range [10] The speed is outside the range set in par. H-72 Warning Speed Low and par.
H-73 Warning Speed High.
Below speed low [11] The output speed is lower than the setting in par. H-72 Warning Speed Low.
Above speed high [12] The output speed is higher than the setting in par. H-73 Warning Speed High.
Out of feedb. Range [13] The feedback is outside the range set in par. H-76 Warning Feedback Low and
par. H-77 Warning Feedback High.
Below feedb. Low [14] The feedback is below the limit set in par. H-76 Warning Feedback Low.
Above feedb. High [15] The feedback is above the limit set in par. H-77 Warning Feedback High.
Thermal warning [16] The thermal warning turns on when the temperature exceeds the limit in the motor,
the frequency converter, the brake resistor or the thermistor.
Mains out of range [17] The mains voltage is outside the specified voltage range.
Reversing [18] The output is high when the frequency converter is running counter clockwise (the logical
product of the status bits "running" AND "reverse").