H-70 Warning Current Low
Range:
0.00 A*
[0.00 - par. H-51 A]
H-71 Warning Current High
3
Range:
par.
AP-37
[par. H-50 - par. AP-37 A]
A*
H-72 Warning Speed Low
Range:
0 RPM*
[0 - par. H-53 RPM]
H-73 Warning Speed High
Range:
par.
H-13
[par. H-52 - par. H-13 RPM]
RPM*
H-74 Warning Reference Low
Range:
-999999.99
[-999999.999 - par. H-75]
9*
H-75 Warning Reference High
Range:
999999.999
[par. H-74 - 999999.999]
*
H-76 Warning Feedback Low
Range:
-999999.99
[-999999.999 - par. H-77]
9*
H-77 Warning Feedback High
Range:
999999.999
[par. H-76 - 999999.999]
*
96
Function:
Enter the I
value. When the motor current falls below this limit, the display reads Current Low. The
LOW
signal outputs can be programmed to produce a status signal on terminal 27 or 29 and on relay output
01 or 02. Refer to the drawing in this section.
Function:
Enter the I
value. When the motor current exceeds this limit, the display reads Current High. The signal
HIGH
outputs can be programmed to produce a status signal on terminal 27 or 29 and on relay output 01 or
02. Refer to the drawing in this section.
Function:
Enter the n
value. When the motor speed exceeds this limit, the display reads Speed Low. The signal
LOW
outputs can be programmed to produce a status signal on terminal 27 or 29 and on relay output 01 or
02.
Function:
Enter the n
value. When the motor speed exceeds this limit, the display reads Speed High. The signal
HIGH
outputs can be programmed to produce a status signal on terminal 27 or 29 and on relay output 01 or
02. Programme the upper signal limit of the motor speed, n
frequency converter. Refer to the drawing in this section.
Function:
Enter the lower reference limit. When the actual reference falls below this limit, the display indicates Ref
Low. The signal outputs can be programmed to produce a status signal on terminal 27 or 29 and on relay
output 01 or 02.
Function:
Enter the upper reference limit. When the actual reference exceeds this limit, the display reads Ref High.
The signal outputs can be programmed to produce a status signal on terminal 27 or 29 and on relay
output 01 or 02.
Function:
Enter the lower feedback limit. When the feedback falls below this limit, the display reads Feedb Low. The
signal outputs can be programmed to produce a status signal on terminal 27 or 29 and on relay output
01 or 02.
Function:
Enter the upper feedback limit. When the feedback exceeds this limit, the display reads Feedb High. The
signal outputs can be programmed to produce a status signal on terminal 27 or 29 and on relay output
01 or 02.
AF-650 GP Programming Guide
, within the normal working range of the
HIGH