Very long control cables and analog signals may in rare cases and depending on installation result in 50/60 Hz earth loops due to noise from mains supply cables.
If this occurs, it may be necessary to break the screen or insert a 100 nF capacitor between screen and chassis.
The digital and analog inputs and outputs must be connected separately to the common inputs (terminal 20, 55, 39) of the frequency converter to avoid ground
currents from both groups to affect other groups. For example, switching on the digital input may disturb the analog input signal.
Input polarity of control terminals
NB!
Control cables must be screened/armoured.
See section entitled Earthing of Screened/Armoured Control Cables for the
correct termination of control cables.