GE AF-650 GP Programming Manual page 49

General purpose drive
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

F-90 Step Size
Range:
0.10 %*
[0.01 - 200.00 %]
F-91 Accel/Decel Time
3
Range:
1.00 s*
[0.00 - 3600.00 s]
F-92 Power Restore
Option:
[0] *
Off
[1]
On
F-93 Maximum Limit
Range:
100 %*
[-200 - 200 %]
F-94 Minimum Limit
Range:
-100 %*
[-200 - 200 %]
F-95 Accel/Decel Ramp Delay
Range:
0*
[0 - 0]
48
Function:
Enter the increment size required for INCREASE/DECREASE, as a percentage of the synchronous motor
speed, n
. If INCREASE/ DECREASE is activated the resulting reference will be increased / decreased by
s
the amount set in this parameter.
Function:
Enter the ramp time, i.e. the time for adjustment of the reference from 0% to 100% of the specified digital
potentiometer function (Increase, Decrease or Clear).
If Increase/ Decrease is activated for longer than the ramp delay period specified in par. F-95 Accel/Decel
Ramp Delay the actual reference will be ramped up / down according to this ramp time. The ramp time
is defined as the time used to adjust the reference by the step size specified in par. F-90 Step Size.
Function:
Resets the Digital Pot-Meter reference to 0% after power up.
Restores the most recent Digital Pot-Meter reference at power up.
Function:
Set the maximum permissible value for the resultant reference. This is advisable if the Digital Pot-Meter
is used for fine tuning of the resulting reference.
Function:
Set the minimum permissible value for the resultant reference. This is advisable if the Digital Pot-Meter is
used for fine tuning of the resulting reference.
Function:
Enter the delay required from activation of the digital pot-meter function until the frequency converter
starts to ramp the reference. With a delay of 0 ms, the reference starts to ramp as soon as INCREASE/
DECREASE is activated. See also par. F-91 Accel/Decel Time.
AF-650 GP Programming Guide