Using a digital input and 10 V as power supply:
Example: The frequency converter trips when the motor temperature is too high.
Parameter set-up:
Set par. F-10 Electronic Overload to Thermistor Trip [2]
Set par. F-12 Motor Thermistor Input to Digital Input [6]
Using an analog input and 10 V as power supply:
Example: The frequency converter trips when the motor temperature is too high.
Parameter set-up:
Set par. F-10 Electronic Overload to Thermistor Trip [2]
Set par. F-12 Motor Thermistor Input to Analog Input 54 [2]
Input
Digital/analog
Digital
Digital
Analog
Supply Voltage
Volt
24 V
10 V
10 V
AF-650 GP Programming Guide
Threshold
Cut-out Values
< 6.6 kΩ - > 10.8 kΩ
< 800Ω - > 2.7 kΩ
< 3.0 kΩ - > 3.0 kΩ
3
39