GE AF-650 GP Programming Manual page 17

General purpose drive
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

[Off]
stops the connected motor. The key can be selected as Enable [1] or Disable [0] via par. K-41 [Off] Button on Keypad. If no external stop function is selected
and the [Off] key is inactive the motor can be stopped by disconnecting the voltage.
[Auto]
enables the frequency converter to be controlled via the control terminals and/or serial communication. When a start signal is applied on the control
terminals and/or the bus, the frequency converter will start. The key can be selected as Enable [1] or Disable [0] via par. K-42 [Auto] Button on Keypad.
2
NB!
An active HAND-OFF-AUTO signal via the digital inputs has higher priority than the control keys [Hand] – [Auto].
[Reset]
is used for resetting the frequency converter after an alarm (trip). It can be selected as Enable [1] or Disable [0] via par. K-43 [Reset] Button on Keypad.
The parameter shortcut
can be carried out by holding down the [Main Menu] key for 3 seconds. The parameter shortcut allows direct access to any parameter.
2.1.3 Quick Transfer of Parameter Settings between Multiple Frequency Converters
Once the set-up of a frequency converter is complete, we recommend that
you store the data in the Keypad or on a PC via Drive Control Tool Software
DCT 10.
Data storage in Keypad:
1.
Go to par. K-50 Keypad Copy
2.
Press the [OK] key
3.
Select "All to Keypad"
4.
Press the [OK] key
All parameter settings are now stored in the Keypad indicated by the progress bar. When 100% is reached, press [OK].
NB!
Stop the motor before performing this operation.
You can now connect the Keypad to another frequency converter and copy the parameter settings to this frequency converter as well.
Data transfer from Keypad to frequency converter:
1.
Go to par. K-50 Keypad Copy
2.
Press the [OK] key
3.
Select "All from Keypad"
4.
Press the [OK] key
The parameter settings stored in the Keypad are now transferred to the frequency converter indicated by the progress bar. When 100% is reached, press [OK].