GE AF-650 GP Programming Manual page 153

General purpose drive
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

[60]
Logic rule 4
[61]
Logic rule 5
[70]
Logic Controller Time-out 3
[71]
Logic Controller Time-out 4
[72]
Logic Controller Time-out 5
[73]
Logic Controller Time-out 6
[74]
Logic Controller Time-out 7
3
[75]
Start command given
LC-03 Reset Logic Controller
Option:
[0] *
Do not reset Logic Controller
[1]
Reset Logic Controller
3.19.2 LC-1# Comparators
Parameters to configure the Logic Controller (LC) comparators. Comparators are used for comparing variables with fixed preset values.
LC-10 Comparator Operand
Array [6]
Option:
[0] *
DISABLED
[1]
Reference
[2]
Feedback
[3]
Motor speed
[4]
Motor Current
[5]
Motor torque
[6]
Motor power
[7]
Motor Rated Voltage
[8]
DC-link voltage
[9]
Motor Thermal
[10]
Drive thermal
[11]
Heat sink temp.
[12]
Analog input AI53
[13]
Analog input AI54
[14]
Analog input AIFB10
[15]
Analog input AIS24V
[17]
Analog input AICCT
[18]
Pulse input FI29
[19]
Pulse input FI33
152
Function:
Retains programmed settings in all group LC-## parameters.
Resets all group LC-## parameters to default settings.
Function:
Choice [1] to [31] are variables which will be compared based on their values. Choice [50] to [186] are
digital values (TRUE/FALSE) where the comparison is based on the amount of time during which they are
set to TRUE or FALSE, respectively. See par. LC-11 Comparator Operator.
Select the variable to be monitored by the comparator.
DISABLED [0] The comparator is disabled.
Reference [1] The resulting remote reference (not local) as a percentage.
Feedback [2] In the unit [RPM] or [Hz]
Motor speed [3] [RPM] or [Hz]
Motor current [4] [A]
Motor torque [5] [Nm]
Motor power [6] [kW] or [hp]
Motor voltage [7] [V]
DC-link voltage [8] [V]
Motor thermal [9] Expressed as a percentage.
Drive thermal [10] Expressed as a percentage.
Heat sink temp [11] Expressed as a percentage.
Analog input AI53 [12] Expressed as a percentage.
Analog input AI54 [13] Expressed as a percentage.
Analog input AIFB10 [14] [V]. AIFB10 is internal 10 V supply.
Analog input AIS24V [15] [V] Analog input AICCT [17] [°]. AIS24V is switch mode power supply: SMPS 24 V.
Analog input AICCT [17] [°]. AICCT is control card temperature.
Pulse input FI29 [18] Expressed as a percentage.
Pulse input FI33 [19] Expressed as a percentage.
AF-650 GP Programming Guide