Keypad Set-Up - GE AF-650 GP Programming Manual

General purpose drive
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

3.2 Keypad Set-Up

Parameter group related to the fundamental functions of the drive, keypad buttons, configuration of the keypad display, copy-cat features, and password
protection.
3.2.1 K-0# Keypad Basic Settings
3
Parameters for configuring basic drives settings.
K-01 Language
Option:
[0] *
English
K-02 Motor Speed Unit
Option:
[0]
RPM
[1] *
Hz
K-03 Regional Settings
Option:
[0]
International
[1] *
US
This parameter cannot be adjusted while the motor is running.
K-04 Operating State at Power-up
Option:
[0]
Resume
[1] *
Forced stop, ref=old
[2]
Forced stop, ref=0
26
Function:
Defines the language to be used in the display.
The frequency converter is delivered with 4 different languages.
Part of Language packages 1 - 4
Function:
This parameter cannot be adjusted while the motor is running.
The display showing depends on settings in par. K-02 Motor Speed Unit and par. K-03 Regional Settings.
The default setting of par. K-02 Motor Speed Unit and par. K-03 Regional Settings depends on which region
of the world the frequency converter is supplied to, but can be re-programmed as required.
NB!
Changing the Motor Speed Unit will reset certain parameters to their initial value. It is recommended to
select the motor speed unit first, before modifying other parameters.
Selects display of motor speed variables and parameters (i.e. references, feedbacks and limits) in terms
of motor speed (RPM).
Selects display of motor speed variables and parameters (i.e. references, feedbacks and limits) in terms
of output frequency to the motor (Hz).
Function:
Sets par. P-07 Motor Power [kW] units to kW and the default value of par. F-04 Base Frequency to 50 Hz.
Sets par. P-09 Slip Compensation units to HP and the default value of par. F-04 Base Frequency to 60 Hz.
Function:
Selects the operating mode upon reconnection of the frequency converter to mains voltage after power
down in Hand (local) operation mode.
Restarts the frequency converter maintaining the same local reference and the same start/stop settings
(applied by [START/STOP]) as before the frequency converter was powered down.
Restarts the frequency converter with a saved local reference, after mains voltage reappears and after
pressing [START].
Resets the local reference to 0 upon restarting the frequency converter.
AF-650 GP Programming Guide

Hide quick links:

Advertisement

Table of Contents
loading