General Technical Data For - GE RSTi-EP Functional Safety Manual

Hide thumbs Also See for RSTi-EP:
Table of Contents

Advertisement

Detailed Descriptions of EP-19xx Modules
5.1 General Technical Data for EP-19xx
Type of connection
Line connection cross-section
Dimensions
Weight
Protection class (DIN EN 60529)
Flammability rating UL 94
Temperature data
Humidity
Air pressure
Vibration resistance
Shock resistance
Potential isolation
Approvals and Standards
All product-specific technical data is available in the corresponding product description.
GFK-2956A
Spring-style
Single-wired
Fine-wired
Height
Width
Depth
80 – 84 g (2.83 – 2.96 oz)
IP 20
V-0
Operation
Storage, transport
Operation, storage, transport
Operation
Storage, transport
5 Hz ≤ f ≤ 8.4 Hz: 3.5 mm (0.14 in) amplitude as per IEC 60068-2-6
8.4 Hz ≤ f ≤ 150 Hz: 1 g (0.04 oz) acceleration as per IEC 60068-2-6
15 g (0.5 oz) for 11 ms, half sinewave, as per IEC 60068-2-27
Test voltage
Pollution severity level
Overvoltage category
cULus Ordinary Locations
cULus Hazardous Locations
Potentially explosive
atmosphere Zone 2
EMC
PLC
FS
November 2017
0.14 – 1.5 mm
(0.01 – 0.06 in
2
– 16)
0.14 – 1.5 mm
(0.01 – 0.06 in
2
(AWG 26 – 16)
120 mm (4.72 in)
(with release lever: 128 mm, 5.04 in)
11.5 mm (0.45 in)
76 mm (2.99 in)
-20 to +60°C (- 4 to +140 °F)
-40 to +85°C (- 40 to +185 °F)
5% to 95 %, non-condensing as per IEC 1131-2
≥ 795 hPa (altitude ≤ 2000 m, 6562 ft)
as per IEC 61131-2
≥ 700 hPa (altitude ≤ 3000 m, 9843 ft)
as per IEC 61131‑2
Max 28.8 V within one channel 500 V DC
field/system
2
II
UL 508, CSA C22.2 No. 0-M91
ISA 12.12.01: 2007
CSA C22.2 No. 213-M1987 (Reaffirmed 2008)
ATEX Directive 94/9/EC, EN 60079-0:2012 and
EN 60079-15:2010
IEC 61000 (partial standards as per the
requirements of IEC 61131‑2)
IEC 61131-2
DIN EN ISO 13849-1, IEC 61508,
IEC 62061
)
(AWG 26
2
)
2
15