GE AF-650 GP Programming Manual page 35

General purpose drive
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

[1] *
Enabled
[2]
Password Protection
K-43 [Reset] Button on Keypad
Option:
[0]
Disabled
3
[1] *
Enabled
[2]
Password Protection
3.2.6 K-5# Copy/Save
Copy parameter settings between set-ups and to/from the keypad.
K-50 Keypad Copy
Option:
[0] *
No copy
[1]
All to Keypad
[2]
All from Keypad
[3]
Size indep. from Keypad
This parameter cannot be adjusted while the motor is running.
K-51 Set-up Copy
Option:
[0] *
No copy
[1]
Copy to set-up 1
[2]
Copy to set-up 2
[3]
Copy to set-up 3
[4]
Copy to set-up 4
[9]
Copy to all
3.2.7 K-6# Password Protection
Parameters for setting the Password Protection for the drive parameters.
K-60 Main Menu Password
Range:
100*
[0 - 999]
K-61 Access to Main Menu w/o Password
Option:
[0] *
Full access
[1]
Read only
[2]
No access
34
Avoids unauthorised start in Auto mode. If par. K-42 [Auto] Button on Keypad is included in the Quick
Menu, then define the password in par. K-65 Quick Menu Password.
Function:
Avoids accidental alarm reset.
Avoids unauthorised resetting. If par. K-43 [Reset] Button on Keypad is included in the Quick Menu, then
define the password in par. K-65 Quick Menu Password.
Function:
Copies all parameters in all set-ups from the frequency converter memory to the Keypad memory.
Copies all parameters in all set-ups from the Keypad memory to the frequency converter memory.
Copy only the parameters that are independent of the motor size. The latter selection can be used to
programme several frequency converters with the same function without disturbing motor data.
Function:
No function
Copies all parameters in the present Programming Set-up (defined in par. K-11 Edit Set-up) to Set-up 1.
Copies all parameters in the present Programming Set-up (defined in par. K-11 Edit Set-up) to Set-up 2.
Copies all parameters in the present Programming Set-up (defined in par. K-11 Edit Set-up) to Set-up 3.
Copies all parameters in the present Programming Set-up (defined in par. K-11 Edit Set-up) to Set-up 4.
Copies the parameters in the present set-up over to each of the set-ups 1 to 4.
Function:
Define the password for access to the Main Menu via the [Main Menu] key. If par. K-61 Access to Main
Menu w/o Password is set to Full access [0], this parameter will be ignored.
Function:
Disables password defined in par. K-60 Main Menu Password.
Prevent unauthorized editing of Main Menu parameters.
Prevent unauthorized viewing and editing of Main Menu parameters.
AF-650 GP Programming Guide

Hide quick links:

Advertisement

Table of Contents
loading