GE AF-650 GP Programming Manual page 119

General purpose drive
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

3.10.3 O-3# Drive Port Settings
Parameters to configure the GE drive port.
O-30 Protocol
Option:
[0] *
Drive
3
[1]
Drive MC
[2]
Modbus RTU
O-31 Address
Range:
1.*
[1. - 126.]
O-32 Drive Port Baud Rate
Option:
[0]
2400 Baud
[1]
4800 Baud
[2] *
9600 Baud
[3]
19200 Baud
[4]
38400 Baud
[5]
57600 Baud
[6]
76800 Baud
[7]
115200 Baud
O-33 Drive Port Parity
Option:
[0] *
Even Parity, 1 Stop Bit
[1]
Odd Parity, 1 Stop Bit
[2]
No Parity, 1 Stop Bit
[3]
No Parity, 2 Stop Bits
O-35 Minimum Response Delay
Range:
10 ms*
[1 - 10000. ms]
O-36 Max Response Delay
Range:
10001. ms*
[11. - 10001 ms]
O-37 Max Inter-Char Delay
Range:
25.00 ms*
[0.00 - 35.00 ms]
118
Function:
Select the protocol for the drive (standard) port.
Function:
Enter the address for the Drive (standard) port.
Valid range: 1 - 126.
Function:
Baud rate selection for the Drive (standard) port.
Function:
Parity and Stop Bits for the protocol par. O-30 Protocol using the Drive Port. For some of the protocols,
not all options will be visible. Default depends on the protocol selected.
Function:
Specify the minimum delay time between receiving a request and transmitting a response. This is used
for overcoming modem turnaround delays.
Function:
Specify the maximum permissible delay time between transmitting a request and receiving a response.
Exceeding this delay time will cause control word time-out.
Function:
Specify the maximum permissible time interval between receipt of two bytes. This parameter activates
time-out if transmission is interrupted.