3.7 H-## High Perf Parameters

Parameter group related to high performance functions in the drive.
3.7.1 H-0# High Perf Operations
3
Parameters to restore factory setting, configure auto reset, fan operation, reverse lock and start mode (catch a spinning load).
H-03 Restore Factory Settings
Option:
[0] *
Normal operation
[2]
Restore Factory Settings
[3]
Boot mode
H-04 Auto-Reset (Times)
Option:
[0] *
Manual reset
[1]
Automatic reset x 1
[2]
Automatic reset x 2
[3]
Automatic reset x 3
[4]
Automatic reset x 4
[5]
Automatic reset x 5
[6]
Automatic reset x 6
[7]
Automatic reset x 7
[8]
Automatic reset x 8
[9]
Automatic reset x 9
[10]
Automatic reset x 10
[11]
Automatic reset x 15
[12]
Automatic reset x 20
[13]
Infinite auto reset
NB!
The motor may start without warning. If the specified number of AUTOMATIC RESETs is reached within 10 minutes, the frequency converter enters Manual reset
[0] mode. After the Manual reset is performed, the setting of par. H-04 Auto-Reset (Times) reverts to the original selection. If the number of automatic resets is
not reached within 10 minutes, or when a Manual reset is performed, the internal AUTOMATIC RESET counter returns to zero.
NB!
Automatic reset will also be active for resetting safe stop function in firmware version < 4.3x.
88
Function:
Use this parameter to specify normal operation, to perform tests or to initialise all parameters except
par. ID-03 Power Up's, par. ID-04 Over Temp's and par. ID-05 Over Volt's. This function is active only when
the power is cycled (power off-power on) to the frequency converter.
Select Normal operation [0] for normal operation of the frequency converter with the motor in the selected
application.
Select Initialization [2] to reset all parameter values to default settings, except for par. ID-03 Power Up's,
par. ID-04 Over Temp's and par. ID-05 Over Volt's. The frequency converter will reset during the next power-
up.
par. H-03 Restore Factory Settings will also revert to the default setting Normal operation [0].
Function:
Select the reset function after tripping. Once reset, the frequency converter can be restarted.
Select Manual reset [0], to perform a reset via [RESET] or via the digital inputs.
Select Automatic reset x 1...x20 [1]-[12] to perform between one and twenty automatic resets after trip-
ping.
Select Infinite Automatic Reset [13] for continuous resetting after tripping.