[131]
Reference 4-20mA
[132]
Feedback 4-20mA
[133]
Motor cur. 4-20mA
[134]
Torq.% lim 4-20 mA
3
[135]
Torq.% nom 4-20 mA
[136]
Power 4-20mA
[137]
Speed 4-20mA
[138]
Torque 4-20mA
[139]
Bus ctrl. 0-20 mA
[140]
Bus ctrl. 4-20 mA
[141]
Bus ctrl 0-20mA t.o.
[142]
Bus ctrl 4-20mA t.o.
[149]
Torque % lim 4-20mA
[150]
Max Out Fr 4-20mA
AN-61 Terminal X30/8 Min. Scale
Range:
0.00 %*
[0.00 - 200.00 %]
AN-62 Terminal X30/8 Max. Scale
Range:
100.00 %*
[0.00 - 200.00 %]
20
mA
/
desired maximum current x
20 − 4
i
.
e
. 10
mA
:
x
100 = 160 %
10
106
par. F-50 Reference Range [Min-Max] 0% = 4 mA; 100% = 20 mA
par. F-50 Reference Range [-Max-Max] -100% = 4mA; 0% = 12 mA; +100% = 20 mA
Feedback 4-20mA: par. F-50 Reference Range [Min-Max] 0% = 4 mA; 100% = 20 mA
par. F-50 Reference Range [-Max-Max] -100% = 4mA; 0% = 12 mA; +100% = 20 mA
Value is taken from par. DR-37 Drive Max. Current. Inverter max. current (160% current) is equal to 20 mA.
The torque setting is related to setting in par. F-40 Torque Limiter (Driving).
The torque setting is related to the motor torque setting.
Taken from par. P-07 Motor Power [kW]
Taken from par. F-53 Maximum Reference. 20 mA = Value in par. F-53 Maximum Reference.
Torque reference related to 160% torque.
An output value set from Network process data. The output will work independently of internal functions
in the frequency converter.
An output value set from Network process data. The output will work independently of internal functions
in the frequency converter.
par. H-74 Warning Reference Low defines the behaviour of the analog output in case of bus time-out.
par. H-74 Warning Reference Low defines the behaviour of the analog output in case of bus time-out.
Torque % Lim 4-20mA: Torque reference. par. F-50 Reference Range [Min-Max] 0% = 4 mA; 100% = 20mA
par. F-50 Reference Range [-Max - Max] -100% = 4 mA; 0% = 12mA; +100% = 20mA
In relation to par. F-03 Max Output Frequency 1.
Function:
Scales the minimum output of the selected analog signal on terminal X30/8. Scale the minimum value as
a percentage of the maximum signal value, i.e. 0 mA (or 0 Hz) is desired at 25% of the maximum output
value and 25% is programmed. The value can never be higher than the corresponding setting in par.
AN-62 Terminal X30/8 Max. Scale if value is below 100%.
This parameter is active when option module OPCGPIO General Purpose I/O Option Module is mounted
in the frequency converter.
Function:
Scales the maximum output of the selected analog signal on terminal X30/8. Scale the value to the desired
maximum value of the current signal output. Scale the output to give a lower current than 20 mA at full
scale or 20 mA at an output below 100% of the maximum signal value. If 20 mA is the desired output
current at a value between 0 - 100% of the ful-scale output, program the percentage value in the pa-
rameter, i.e. 50% = 20 mA. If a current between 4 and 20 mA is desired at maximum output (100%),
calculate the percentage value as follows:
100 %