[61]
Logic rule 5
[70]
Logic Controller Time-out 3
[71]
Logic Controller Time-out 4
[72]
Logic Controller Time-out 5
[73]
Logic Controller Time-out 6
[74]
Logic Controller Time-out 7
[75]
Start command given
LC-41 Logic Rule Operator 1
Array [6]
Option:
[0] *
DISABLED
[1]
AND
[2]
OR
[3]
AND NOT
[4]
OR NOT
[5]
NOT AND
[6]
NOT OR
[7]
NOT AND NOT
[8]
NOT OR NOT
LC-42 Logic Rule Boolean 2
Array [6]
Option:
[0] *
False
[1]
True
[2]
Running
[3]
In range
[4]
On reference
[5]
Torque limit
[6]
Current Limit
[7]
Out of current range
[8]
Below I low
[9]
Above I high
[10]
Out of speed range
[11]
Below speed low
[12]
Above speed high
[13]
Out of feedb. range
[14]
Below feedb. low
[15]
Above feedb. high
[16]
Thermal warning
[17]
Line voltage out of range
Function:
Select the first logical operator to use on the Boolean inputs from par. LC-40 Logic Rule Boolean 1 and
par. LC-42 Logic Rule Boolean 2.
[LC-##] signifies the boolean input of par. LC-##.
Ignores par. , par. LC-43 Logic Rule Operator 2, and par. LC-44 Logic Rule Boolean 3.
Evaluates the expression [LC-40] AND [LC-42].
evaluates the expression [LC-40] OR[LC-42].
evaluates the expression [LC-40] AND NOT [LC-42].
evaluates the expression [LC-40] OR NOT [LC-42].
evaluates the expression NOT [LC-40] AND [LC-42].
evaluates the expression NOT [LC-40] OR [LC-42].
evaluates the expression NOT [LC-40] AND NOT [LC-42].
evaluates the expression NOT [LC-40] OR NOT [LC-42].
Function:
Select the second boolean (TRUE or FALSE) input for the selected logic rule. See par. LC-01 Start Event ([0]
- [61]) and par. LC-02 Stop Event ([70] - [75]) for further description.
AF-650 GP Programming Guide