GE AF-650 GP Programming Manual page 109

General purpose drive
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

3
[0] *
No function
[1]
Ctrl. Decel
[2]
Ctrl. Decel, trip
[3]
Coasting
[4]
Kinetic back-up
[5]
Kinetic back-up, trip
[6]
Alarm
SP-11 Line Voltage at Input Fault
Range:
342. V*
[180 - 600 V]
SP-12 Function at Line Imbalance
Operation under severe main imbalance conditions reduces the lifetime of the motor. Conditions are considered severe if the motor is operated continuously
near nominal load (e.g. a pump or fan running near full speed).
Option:
[0] *
Trip
[1]
Warning
[2]
Disabled
108
Kinetic Back-up [4]: The frequency converter will keep on running as long as there is energy in the system
due to the moment of inertia produced by the load.
Kinetic Back-up [5]: The frequency converter will ride through on speed as long as the energy is present
from moment of inertia from the load. If the DC voltage goes below par. SP-11 Line Voltage at Input
Fault the frequency converter will perform a trip.
Function:
This parameter defines the threshold voltage at which the selected function in par. SP-10 Line failure
should be activated.
Function:
Trips the frequency converter
Issues a warning
No action
AF-650 GP Programming Guide