(1) A cycle crossing occurs since the D/A conversion has been processed across the inter-module synchronization cycle. After that, the D/A converter module
immediately stops the synchronized operation.
When a cycle crossing has occurred, follow the methods below to resolve the issue.
• The inter-module synchronization cycle may be shorter for the time needed for the D/A conversion. Set a
longer inter-module synchronization cycle so that the D/A conversion is completed within the inter-module
synchronization cycle.
• The possible cause is that the execution time for an inter-module synchronous interrupt program (I44) is
longer. Correct settings such as reducing the number of steps of the inter-module synchronous interrupt