Error code
Error name
2600H
Inter-module synchronization
cycle crossing over error
2601H
Inter-module synchronization
cycle skip error
2610H
Inter-module synchronization
signal error
3001H
Hardware error
3030H
Flash memory error
*1 The error code is not stored in 'Latest error code' (Un\G0). It is stored in completion status area (S)+1 of the G(P).OGSTOR instruction.
In addition, 'Error flag' (XF) does not turn on.
Description and cause
It was detected that the processing was performed
across the cycles with the inter-module
synchronization function operating.
It was detected that the processing of a cycle was
skipped with the inter-module synchronization
function operating.
A synchronization loss was detected with the inter-
module synchronization function operating.
A hardware error has occurred in the module.
The data in the flash memory is abnormal.
Action
Correct settings to extend the inter-module
synchronization cycle or reduce the number of steps
of the inter-module synchronous interrupt program.
• Execute the EI instruction in the main program
and enable an interrupt.
• Correct settings to extend the inter-module
synchronization cycle or reduce the number of
steps of the inter-module synchronous interrupt
program.
If the error occurs again even after the above actions
are taken, the possible cause is a failure of the
module. Please consult your local Mitsubishi
representative.
The module may be affected by noise. Check and
adjust the cable wiring and the installation
environment of the programmable controllers, and
restart the system. If the error occurs again even
after the adjustment, the possible cause is a failure
of the module. Please consult your local Mitsubishi
representative.
Power off and on the module. If the error occurs
again, the possible cause is a failure of the module.
Please consult your local Mitsubishi representative.
Check an analog output value. If the value is
abnormal, please consult your local Mitsubishi
representative.