How to register data when a remote head module is used
For how to register the wave data and parameter settings for the wave output function, which is created from "Create Wave
Output Data" of the engineering tool, in the D/A converter module, refer to the following.
■Registration procedure
1.
Write wave data and parameters for the wave output function to the file register (ZR) of the CPU module on the master
station using "Create Wave Output Data" of the engineering tool.
2.
Transfer the data and parameters from the file register (ZR) to the D/A converter module mounted with the remote head
module using the JP.REMTOD instruction.
Register the wave data and parameters for the wave output function first, and then change 'CH1 D/A conversion enable/
disable setting' (Un\G500).
3.
Request a wave output start/stop through a program.
■Program
This program is used to transfer the data and parameters from the file register (ZR) to the D/A converter module mounted with
the remote head module using the JP.REMTOD instruction. The program in this section is described under the assumption
that the data is written from "Create Wave Output Data" regarding the start device as ZR0. Depending on the specified start
device, the file register (ZR) to which the parameter settings of the wave output function and wave data are written varies. For
details on the file register (ZR) to which the data is written, refer to the following.
 MELSEC iQ-R Analog-Digital Converter Module/Digital-Analog Converter Module Function Block Reference
• System configuration
(1)
(1) Master station (Network number 1, station number 0)
• Power supply module: R61P
• CPU module: R04CPU
• Master/local module: RJ71GF11-T2 (Start I/O number: 0000H to 001FH)
• Input module: RX10 (Start I/O number: 0020H to 002FH)
(2) Intelligent device station (Network number 1, station number 1)
• Power supply module: R61P
• Remote head module: RJ72GF15-T2
• D/A converter module: R60DAH4 (Start I/O number: 0000H to 000FH
*1 In the RX/RY setting of the master station, set 1000H to 100FH as the start I/O number of the D/A converter module.
1 FUNCTIONS
64
1.14 Wave Output Function
(2)
*1
)