Mitsubishi Electric MELSEC iQ-R Series User Manual page 101

High speed digital-analog converter module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Warning output during synchronization
Regarding the warning output while the inter-module synchronization function is enabled, the update timing for ALM LED,
'Warning output signal' (XE), 'Warning output upper flag' (Un\G36), and 'Warning output lower flag' (Un\G37) are changed as
described below.
Inter-module
synchronization cycle
Program
Inter-module synchronous
interrupt program
'CH1 Synchronization
digital value' (Un\G9500)
Analog output
value in CH1
2A
Warning output upper
limit value in CH1
Warning output lower
limit value in CH1
3A
ALM LED
'Warning output signal'
OFF
(XE)
CH1 Warning output upper
flag (Un\G36.b0)
CH1 Warning output lower
flag (Un\G37.b0)
Digital value
Analog output value
Inter-module synchronous interrupt program (I44)
(1) ALM LED turns on when a D/A conversion is completed (during warning detection).
(2) 'Warning output signal' (XE) is refreshed at the start of the synchronous interrupt program.
(3) 'Warning output upper flag' (Un\G36) and 'Warning output lower flag' (Un\G37) are refreshed at the END processing.
Inter-module
synchronization cycle
END
1A
2A
(1)
Off
ON
(2)
0
END
3A
On
0
(3)
1.15 Inter-Module Synchronization Function
END
4A
1
1
1 FUNCTIONS