Mitsubishi Electric MELSEC iQ-R Series User Manual page 185

High speed digital-analog converter module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Offset/gain adjustment value specification
Normal
Set the adjustment amount of the analog output value in the offset/gain setting mode.
For details on the offset/gain setting, refer to the following.
 MELSEC iQ-R High Speed Digital-Analog Converter Module User's Manual (Startup)
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
Offset/gain adjustment value specification
■Setting range
The setting range is from -3000 to 3000.
Ex.
When the setting value is 1000
Analog output values are adjusted as shown below.
User range setting
User range setting (voltage)
User range setting (current)
■Enabling the setting
Turn on 'Set value change request' (YC).
■Default value
The default value is 0.
CH1
CH2
4130
Analog output value
Approx. 0.31V
Approx. 0.35mA
CH3
CH4
APPX
Appendix 3 Buffer Memory Areas
A
183

Advertisement