General - Operating Mode After Reset; General - Send Cyclic "In Operation" (Min) - ABB i-bus KNX Product Manual

Room temperature controller
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

11.5.9

General - Operating mode after reset

Options:
After a reset the device will run in the operating mode after a restart until a new operating mode
is set as the result of device operation or by communication objects, as the case may be. This
operating mode should be defined during the planning phase. An improperly defined operating
mode can result in a loss of comfort or increased energy consumption.
Comfort : If the room temperature is not automatically lowered and the room is therefore
controlled independent of its use.
Standby : If the room is controlled automatically, e.g. by a presence detector, as a function of
its use.
Eco mode : If the room is controlled automatically or manually as a function of its use.
Frost/heat protection : If only the building protection function is necessary in the room after a
reset.
Note
This parameter is only available if the "Device function" parameter is set on
"Single device" or "Master device".
11.5.10 General — Send cyclic "In operation" (min)
Options:
Communication object "In operation" serves for the information that the controller still
operates. Value "1" is sent cyclic. The cycle for sending is set via this parameter. If there is
no cyclic telegram, the function of the device is disturbed and the air-conditioning of the
room can be maintained via forced control. For this, however, the system and/or actuator
must have the "Forced control" function.
Product manual 2CKA001473B9482
Description of application and parameters
Comfort
Standby
Eco mode
Frost/heat protection
Setting option between 5 - 3000 minutes
Application "Function block RTC"
│79