11.5.110 Temperature reading — Adjustment value for internal temperature measurement (x
0.1°C)
Options:
Every installation location has different physical conditions (interior or exterior wall, lightweight
or solid wall, etc.). In order to use the actual temperature at the installation location as a
measured value for the device, a temperature measurement must be performed by an external
equalised and / or calibrated thermometer at the installation location. The difference between
the actual temperature displayed on the device and the actual temperature determined by the
external measurement device must be entered in the parameter field as an "Adjustment value".
Note
11.5.111 Temperature reading — Monitoring time for temperature reading (0 = no monitoring)
(min)
Options:
If no temperature is read within the parameterized time period, the device switches to error
mode. It transmits a telegram to the bus via the "Actual temperature error" object and applies
the operating mode and control value for error (0 - 255) settings.
11.5.112 Temperature reading — Control value for fault (0 - 255)
Options:
In the event of a failure of the actual temperature measurement, the device will no longer be
able to independently determine the control value. In case of an error, a PWM control (1 Bit)
with a fixed cycle time of 15 minutes is used automatically instead of a parameterized 2-point
control (1 Bit). In this case the set parameter value is taken into consideration for the control
value during an error.
Product manual 2CKA001473B9482
Description of application and parameters
Setting option between 1 - 100
The calibration measurement should not be carried out immediately after the
device has been installed. The device should first adjust to the ambient
temperature before calibration is carried out. The calibration measurement
should be repeated shortly before or after the room is occupied.
This parameter is only available when the "Inputs of temperature reading"
parameter is set on "Internal measurement" or "Weighted measurement".
Setting option between 0 - 120
Setting option between 0 - 255
Application "Function block RTC"
│116