11.6.7.3

Delay time

Options:
The parameter is used to set the delay with which the telegrams received via object "GFx: input"
are sent via object "GFx: output".
The delay time can be set in steps of one millisecond.
11.6.7.4

Retriggering

Options:
Deactivated:
The set switch-off delay always runs to its end, so that a telegram is always sent via
object "GFx: output" after the delay time has expired.
Activated:
The switch-off delay is always restarted when a telegram is received via the "GFx: input"
object.
The parameter is used to specify whether the switch-off delay is restarted when a further
telegram is received via object "GFx: input". This behaviour is called retriggering.
For example, a retriggering makes sense for a switch-off delay for movement detectors. This
always resets the switch-off delay as long as movement is detected.
If telegrams with different values are received during the retriggering phase, only the last value
received is always sent via the "GFx: output" object after expiration of the delay time.
11.6.7.5

Filter active

Options:
Deactivated:
Filter is not active.
Activated:
Filter is active. Filter function and filter value can be set.
The parameter is used to specify whether a filter is used for the delay of telegrams.
Product manual 2CKA001473B9482
Description of application and parameters
Setting option from 00:00:01.000 to 01:00:00:000 (hh:mm:ss)
Deactivated
Activated
Deactivated
Activated
Application "General functions"