Value Of The Output Object For Logic Untrue; Output Default Value Untrue - ABB i-bus KNX Product Manual

Room temperature controller
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

11.6.4.12

Value of the output object for logic untrue

Options:
Output is set on 0:
As soon as the logic function is fulfilled, a logical "0" is present on the output. This
equally applies when the "Object type output" parameter is set on "1 byte".
Defined via output default value untrue:
The value that is present on the output when the logic has been met, can be set via
parameter "Output default value untrue".
The parameter is used to specify the value that is sent via object "GFx: output" when a condition
(untrue) has not been met.
11.6.4.13

Output default value untrue

Options:
Untrue = 0
When a logic has not been met, value "0" is present at communication object "GFx:
output".
Untrue = 1
When a logic has not been met, value "1" is present at communication object "GFx:
output".
The parameter is used to specify the value that is sent via the 1-bit communication object "GFx:
output" when a condition (untrue) has been not been met.
Note
The parameter can only be set if the "Object type output" parameter is set on "1
bit" and parameter "Value of the output object for logic untrue" is set on "Defined
via output default value untrue".
11.6.4.14
Output default value untrue
Options:
The parameter is used to set the value that is sent via the 1-byte communication object "GFx:
output" when a condition (untrue) has been not been met.
Note
The parameter can only be set if the "Object type output" parameter is set on "1
byte" and parameter "Value of the output object for logic untrue" is set on
"Defined via output default value untrue".
Product manual 2CKA001473B9482
Description of application and parameters
Output is set to 0
Defined via output default value untrue
Untrue = 0
Untrue = 1
Setting option from 0 to 255
Application "General functions"
│152