11.5.98 Setpoint adjustment — Maximum manual reduction during cooling mode (0 - 9°C)
Options:
This preset can be used to limit the manual decrease during cooling.
Note
This parameter is only available when the "Control function" parameter is set on
"Cooling," "Cooling with additional stage," "Heating and cooling" or "Heating and
cooling with additional stages".
11.5.99 Setpoint adjustment — Resetting of the manual adjustment for receipt of a basic
setpoint
Options:
Activating this parameter will cause the manual adjustment to be deleted and the new setpoint
value to be provided when a new value is received via the "Basic setpoint" object.
If the parameter is deactivated, the manual adjustment is added to the new base setpoint value.
Example: Previous base setpoint value of 21°C + manual adjustment of 1.5°C = 22.5°C. The
object receives a new basic setpoint of 18°C plus the previous manual adjustment of 1.5°C for a
total of 19.5°C.
11.5.100 Setpoint adjustment — Resetting the manual adjustment for change of operating mode
Options:
If the device switches to a new operating mode, the manual adjustment is deleted and the
parameterized setpoint temperature for the operating mode plus any change by the base
setpoint value object will be applied if this parameter is activated. Example: Comfort
temperature of 21°C plus manual adjustment of 1.5°C = 22.5°C. Change to Eco with
programmed temperature 17°C. The device regulates the temperature to 17°C, since the
manual adjustment is deleted.
If the parameter is deactivated, the manual setpoint adjustment will be added to the temperature
in the new operating mode. Example: Comfort temperature of 21°C plus manual adjustment of
1.5°C = 22.5°C. If the system switches to Eco with a parameterized temperature of 17°C, the
device regulates the temperature to 18.5°C, since the manual adjustment is added.
Product manual 2CKA001473B9482
Description of application and parameters
Setting option between 0 - 9
No
Yes
No
Yes
Application "Function block RTC"