11.5.136 Summer compensation — (Upper) exit temperature for summer compensation (°C)
Options:
The parameter defines the upper outside temperature value up to which temperature value the
setpoint correction (summer compensation) is performed based on too high an outside
temperature.
Note
This parameter is only available if the "Summer compensation" parameter is set
to "Yes".
11.5.137 Summer compensation — Offset of the set-point temperature for the exit from summer
compensation (x 0.1°C)
Options:
The parameter is used to define how many degrees Kelvin the setpoint value will be increased
by during summer compensation when the upper temperature value is reached.
Typical values for summer compensation are:
20°C: Lower outside temperature value
32°C: Upper outside temperature value
0 K: Lower setpoint offset
4 K: Upper setpoint offset
That means that a flowing setpoint increase of 0 to 4 K occurs if the outside temperature
increases from 20°C to 32°C.
Note
This parameter is only available if the "Summer compensation" parameter is set
to "Yes".
Product manual 2CKA001473B9482
Description of application and parameters
Setting option between -127 - 127
Setting option between -127 - 127